6423 Centralized Control Emergency Sign Luminaires-Explosion-proof Sign Lamp

It features independent address encoding, and can perform real-time on-site monitoring of the light source faults of marker lamps and report the light source status to the control host.

Multiple high-quality ultra-bright LEDs are used as the light source, which has high brightness, long lifespan, and low power consumption.

Technical Specifications

Communication mode: Bus communication

Operating voltage: DC36V (pulse DC21V~DC36V)

Main power consumption: 1W

Emergency working time: ≥90 minutes, Emergency conversion time: ≤5S

Light source name and parameters: LED, DC3.0V

Mark surface brightness: 50cd/m²~300cd/m²

Working mode: Continuous type

Emergency control mode: Centralized control type

Emergency power supply mode: Centralized power supply type

Coding mode: Electronic coding

Wiring system: Non-polar two-wire bus

Shell material: Cast aluminum

Shell protection level: IP65

Execution standards: GB17945-2010, GB3836.1-2010, GB3836.2-2010

Operating environment:

Temperature: 0°C~55°C, Relative humidity:<95%, without condensation

Installation method: Wall-mounted installation