6410E Centralized Control Type Fire Emergency Sign Luminaires

This device has a stainless steel panel and a flame-retardant plastic shell. It uses high-quality LEDs for high brightness, long life, and low power consumption. It features independent address coding to monitor and report light source failures, employs electronic coding with a handheld encoder and a two-wire non-polar connection for easy debugging, and has strong anti-interference ability.

Technical Specifications

Communication Method: Bus Communication

Working Voltage: DC36V (Pulse DC21V – DC36V)

Main Power Consumption: 0.5W

Emergency Working Time: ≥ 90 minutes, Emergency Conversion Time: ≤ 5s

Light Source Name and Parameters: LED, DC3.0V, 0.1W

Surface Brightness: 50 – 300 cd/m²

Working Mode: Continuous Type

Emergency Control Method: Centralized Control Type

Emergency Power Supply Method: Centralized Power Supply Type

Coding Method: Electronic Coding Method

Wiring System: Non-polar Two-wire Bus

Case Material: Flame-retardant Plastic Case, Stainless Steel Panel

Enclosure Protection Grade: IP67

Implementation Standards: GB17945-2010

Operating Environment: Temperature: 0°C – 55°C, Relative Humidity: ≤ 95%, No Condensation

Installation Method: Floor Installation