TR3106A Household Combustible Gas Detector

Have sound and light alarm functions.

Have two output modes: active and passive.

Automatic sensor life detection.

After an alarm, when the gas concentration is lower than the alarm set value, the detector automatically recovers (the solenoid valve needs to be manually reset after activation).

Have a network expansion interface.

Have historical data recording and reading functions.

Use a wall-mounted installation method, which is simple to install and convenient to use.

Category:

Technical Specifications

Working voltage: AC220V, 50Hz

Power consumption: Normal monitoring state ≤ 2.0W, Alarm state ≤ 2.5W

Output mode: 1 group of DC12V (pulse output, the output interface’s load-carrying current ≤ 140mA), 1 group of switching value output (contact capacity DC30V/1A)

Applicable gas: Propane

Measuring range: 0~20% LEL

Alarm set value: 8% LEL

Sensor service life: 5 years (typical value)

Power-on preheating time: 20 minutes

Operating environment: -10°C~+55°C, ≤95%RH, without condensation

Color: White

Weight: 145g

Dimensions: 858535mm (including base)